Design case of access control system for Olympic venues

SaveSavedRemoved 0
Deal Score0
Deal Score0

[ad_1]

The Olympic projects mainly consist of some venue projects. The venue projects are very different from ordinary buildings. They mainly show the characteristics of large area, large space span, building layers, equipment and computer rooms, etc.; at the same time, the application situation shows that it may be idle at ordinary times. Once used, it is a peak application, which requires a high load on the system.

  
Access control point distribution design

The main function of the access control system of the Olympic venues is to prevent illegal personnel from trailing into the controlled area and to ensure the normal development of the event. The access control points of Olympic venues are mainly distributed in important computer rooms, communication rooms, VIP rooms, media offices, Olympic organizing committee offices, doping control centers, competition offices, athletes rooms, locker rooms, etc.

  The overall requirements of the access control system

The access controller should have an independent controller and memory. The system can run offline and independently, and the system can automatically upload information when the communication with the server is restored. The system adopts TCP/IP networking mode, or RS485 mode according to the situation.

System access control cards generally use 13.56MHZ radio frequency identification cards, which are dynamically encrypted between the card and the card reader to prevent information from being stolen. The access control data is stored in a separate sector of the card, and other sectors can be used for all-in-one card applications as needed.

Electric locks are selected and used according to the on-site situation. In the Olympic venues, single-door, double-door electromagnetic locks, electric bolt locks and emergency escape locks are more commonly used. Use the door sensor to monitor the opening and closing of the door, opening the door too long, and forcibly opening the door.

Set up access control workstations in the main control room and sub-control rooms to monitor the front-end field equipment in real time. Once the door is forced to open or the door is opened for a long time, it can automatically alert on the access control workstation, and an electronic map can be displayed to display the alarm location. It can be linked to the TV monitoring system to facilitate managers to understand the situation on the spot.

  
Integration requirements for access control systems

There may be two situations for the integration requirements of the access control system in the Olympic venues. One is the traditional IBMS integration, and the integration of the access control with the fire protection, building control, and monitoring systems to achieve system information sharing and cross-system linkage. This integration The method requires real-time, reliability, and interactivity.

Another requirement is the integration of the Olympic command platform. The purpose of this integration is to monitor the status of the access control system on the Olympic command platform. The Olympic command platform generally integrates multiple venues and multiple systems. Its purpose is to integrate information resources related to the Olympics on a large platform, and its main function is information collection. In actual use, it is generally; monitor but not control; .

 
IBMS integration in Olympic venues

IBMS integration mainly includes weak electronic systems such as access control, monitoring, anti-theft, and fire protection.

Integration of access control system and TV monitoring system:

The access control system and the matrix system are generally integrated by serial protocol. The access control system server and the matrix are connected through the serial port. When an access alarm event occurs, such as invalid card swiping, door opening time is too long, forced door breaking, etc., the access control system server sends it through the serial port The ASII protocol commands are given to the matrix host, and the matrix host implements PTZ, preset call, image switching and other operations in accordance with the protocol commands.

Integration of access control system and DVR system:

Access control system and DVR system generally adopt API method to integrate. Through API, the access control system can send alarm information to DVR system, and can call DVR video image and control PTZ through the network; DVR system can receive the alarm information of the access control system. Perform linkage operations.

Integration of access control system and fire protection system:

The linkage between the access control system and the fire protection system generally adopts dry joint hard linkage to ensure safety and reliability. The fire alarm signal is output to the access control system to receive. Once the fire alarm is triggered, the access control system can automatically open the access control of the corresponding area, which is convenient for people to escape urgently; at the same time, the access control The passage is conducive to the disposition of glass breaking buttons on the escape side, so people can escape urgently.

Integration of access control system and building automatic control system:

Unlike building control systems, access control systems generally use OPC or ODBC. Through the OPC interface, the numbers of related parameters in the related database can be read or written to change other systems or the state of a certain device by other systems; through the ODBC method, the database form can be imported or exported, and the underlying protocol Edit to make your own hardware devices communicate with other software.

1

[ad_2]

We will be happy to hear your thoughts

Leave a reply

RFID made in China
Logo
Enable registration in settings - general
Compare items
  • Cameras (0)
  • Phones (0)
Compare